Features and Benefits
Active communication with patented Active OPC Server
2-port Ethernet switch for daisy-chain topologies
Easy mass deployment and configuration with ioSearch utility
Save time and wiring cost with peer-to-peer communication
User-defined Modbus/TCP addressing
Simplify I/O managment with MXIO library on either Windows or Linux platform
Supports SNMPv1/v2c
UL/cUL Class I Division 2, ATEX Zone 2 certification
Wide operating temperature: -40 to 75°C ( -40 to 167°F )
Introduction
Daisy-chained Ethernet I/O Connection
A new daisy-chained Ethernet I/O concept is now available. The ioLogik E1210 industrial Ethernet remote I/O has two embedded Ethernet switch ports that allow information to flow to another local Ethernet device or connect to the next ioLogik in the daisy-chain.
Applications such as factory automation, security and surveillance systems, and tunnel monitoring, can make use of daisy-chained Ethernet for building multi-drop I/O networks over standard Ethernet cables. Many industrial automation users are familiar with the multi-drop configuration typically used in fieldbus applications. The daisy-chain function on the Ethernet remote I/O ioLogik E1210 not only increases the connection between machines and panels, but also lowers the cost of buying separate Ethernet switches, and at the same time reduces labor fees and cabling by a large percentage. For example, if a production facility contains 700 stations (20 points per station), the wiring cost reduction can reach 15% of the total implementation cost.
Saving Time and Wiring Costs with Peer-to-Peer Communications
In remote automation applications, the control room and sensors are often far removed, making wiring over long distances a constant challenge. With peer-to-peer networking, users may now map a pair of ioLogik E1200 series modules so that input values will be directly transferred to output channels, greatly simplifying the wiring process and reducing wiring costs.
User-definable Modbus/TCP Addressing for Painless Upgrading of Existing Systems
For Modbus devices that are controlled and detected by fixed addresses, users need to spend a vast amount of time researching and verifying the configurations. Users need to locate each device’s networking details like I/O channels, or vendor-defined addresses to enable the initial or start address of a SCADA system or PLC. The ioLogik E1200, with user-definable Modbus/TCP addressing, offers greater flexibility, and setup is easy. Instead of worrying about individual devices, users simply configure the function and address map to fit their needs.
• Inputs and Outputs | |
Digital Inputs | 6 channels |
Relay Outputs | 6 channels |
• Digital Input | |
Sensor Type | Wet Contact (NPN or PNP), Dry Contact |
I/O Mode | DI or Event Counter |
Dry Contact |
• On: short to GND • Off: open |
Wet Contact |
• On: 0 to 3 VDC • Off: 10 to 30 VDC |
Isolation | 3K VDC or 2K Vrms |
Counter Frequency | 250 Hz, power off storage |
• Relay Output | |
Type | Form A (N.O.) relay outputs, 5A |
Contact Rating | 5 A @ 30 VDC, 5 A @ 250 VAC, 5 A @ 110 VAC |
Inductance Load | 2 A |
Resistance Load | 5 A |
Breakdown Voltage | 500 VAC |
Relay On/Off Time | 1500 ms (Max.) |
Initial Insulation Resistance | 1G min. @ 500 VDC |
Expected Life | 100,000 times (Typical) |
Initial Contact Resistance | 30 milli-ohms (Max.) |
Pulse Output | 0.3 Hz at rated load |
• LAN | |
Ethernet | 2 x 10/100 Mbps switch ports, RJ45 |
Protection | 1.5 KV magnetic isolation |
Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP |
• Power Requirements | |
Power Input | 24 VDC nominal, 12 to 36 VDC |
Power Consumption | 188 mA @ 24 VDC |
• Physical Characteristics | |
Wiring | I/O cable max. 14 AWG |
Dimensions | 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in) |
Weight | under 200 g |
• Environmental Limits | |
Operating Temperature |
Standard Models: -10 to 60°C (14 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Altitude | Up to 2000 m and higher altitude on demand |
• Standards and Certifications | |
Safety | UL 508 |
EMI | FCC Part 15 Subpart B Class A |
EMS | IEC 61000-4, IEC 61000-6 |
Shock | IEC 60068-2-27 |
Freefall | IEC 60068-2-32 |
Vibration | IEC 60068-2-6 |
Hazardous Location | UL/cUL Class I Division 2, ATEX Zone 2 |
• MTBF (mean time between failures) | |
Time | 808,744 hrs |
Database | Telcordia (Bellcore) |
• Warranty | |
Warranty Period | 2 years |
Details | See www.moxa.com/warranty |