ioLogik E1510-T


psp_ra_banner
  • Compliant with EN 50121-3-2, EN 50121-4 and essential sections of EN 50155
  • Wide operating temperature: -40 to 85°C (-40 to 185°F)
  • Channel-to-Channel isolation (DI Only)
  • Robust and compact design for harsh environment
  • Active communication with patented Active OPC Server
  • User-defined Modbus/TCP addressing
  • Friendly configuration via web browsers

Introduction

The ioLogik E1510 Ethernet Remote I/O product has a ruggedized aluminum housing, and is compliant with EN 50121-3-2, EN 50121-4 and essential sections of EN 50155 standard, both of which are essential for electronic equipment used in rolling stock applications. This rugged platform features a wide operating temperature range of -40 to 85°C to deliver consistent performance in harsh environment.

WT

DI Channel Isolation Protection

Channel to channel isolation provides the most robust protection against electrical surges. With this topology, each DI channel on the ioLogik E1510 is individually isolated to ensure highly stable data communication. In cases of high surge events such as lighting strikes, the device is protected from current surge by this channel isolation feature. This is a critical requirement in railway applications when considering an Ethernet-based I/O solution.

diagram(3)

Seamless SCADA Connectivity with Active OPC Technology

Moxa’s patented Active OPC Server is a software package that operates as an OPC driver for HMI and SCADA systems . The Active OPC server enables the ioLogik E1510 to actively communicate with the SCADA system to provide instant I/O status.

AOPC(2)

 

ioLogik E1500-dimen
LAN
Ethernet 1 10/100 Mbps switch port, M12
Protection 1.5 KV magnetic isolation
Protocols Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP
Inputs and Outputs
Digital Inputs 12 channels (channel-to-channel isolation)
Isolation 3K VDC or 2K Vrms
Digital Input
Sensor Type Wet Contact (NPN or PNP), Dry Contact
I/O Mode DI or Event Counter
Dry Contact • On: short to GND
• Off: open
Wet Contact (DI to GND) • On: 0 to 3 VDC
• Off: 10 to 30 VDC
Counter Frequency 250 Hz, power off storage
Digital Filtering Time Interval Software selectable (minimum: 1 millisecond)
Power Requirements
Power Input 24 VDC nominal, 12 to 48 VDC
Power Consumption 163 mA @ 24 VDC
Physical Characteristics
Wiring I/O cable max. 14 AWG
Dimensions 144 x 124 x 30 mm (5.67 x 4.88 x 1.18 in)
Weight 825 g
Mounting DIN rail (standard), wall (with optional kit)
Environmental Limits
Operating Temperature -40 to 85°C (-40 to 185°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Altitude Up to 2000 m and higher altitude on demand
Standards and Certifications
Safety UL 508
EMI EN 61000-3-2, EN 61000-3-3, EN 61000-6-4, FCC Part 15 Subpart B Class A
EMS EN 55024, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11,
EN 61000-6-2
Shock IEC 60068-2-27
Freefall IEC 60068-2-32
Vibration IEC 60068-2-6
Rail Traffic EN 50155, EN 50121-3-2, EN 50121-4
Green Product RoHS, CRoHS, WEEE
Note Please check Moxa’s website for the most up-to-date certification status.
Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty