Features and Benefits
- 8 analog input channels for millivolts ( ›› mV), voltage, and current signal with wire-off detection (at 4 to 20 mA)
- 2-channel analog outputs for voltage, current actuator control
- 16-bit resolution analog inputs, 12-bit resolution analog output
- Easy-to-use, quick programming library for VB, VC++, BCB, .NET
- NIST-Traceability calibration for analog I/O channels
- Firmware upgradable over RS-485
Introduction
Linking Input and Output Signals over a Serial Connection
The ioLogik R2000/4000 series was designed for system integrators to acquire and control remote digital and analog devices over both RS-232 and RS-485 connections. Different types of digital on/off devices can be controlled, including proximity switches, mechanical switches, push buttons, optical sensors, LEDs, and light switches. In addition, different types of analog devices can be controlled, including sensors that read pH, conductivity, temperature, humidity, pressure, and flow, as well as actuators and valves. ioLogik R2000/4000 series products can be used with the standard Modbus protocol, and SCADA software or the MXIO DLL library can be used to access the server.
Easy Remote Management
Traditionally, it was difficult for users to update firmware over RS-485. Moxa now provides an easy method for updating firmware over an RS-485 network that allows users to perform remote firmware updates, reducing maintenance time and cost.

• Inputs and Outputs | |
Analog Inputs | 8 channels |
Analog Outputs | 2 channels |
• Analog Input | |
Resolution | 16 bits |
I/O Mode | Voltage / Current |
Input Range | ±150 mV, ±500 mV, ±5 V, ±10 V, 0 to 20 mA, 4 to 20 mA |
Accuracy |
±0.1% FSR @ 25°C ±0.3% FSR @ -10 and 60°C |
Sampling Rate |
Sample Rate: (for Voltage) All Channels: 10 samples/sec Per Channel: 1.25 samples/sec One one channel enabled: 1.25 samples/sec Sample Rate: (for Current) All Channels: 6 samples/sec Per Channel: 0.75 samples/sec One one channel enabled: 0.75 samples/sec |
Built-in Resistor for Current Input | 106 ohms |
Isolation | 3K VDC or 2K Vrms |
• Analog Output | |
Resolution | 12 bits |
Output Range | 0 to 10 V, 4 to 20 mA |
Drive Voltage | 15 VDC for current output |
Accuracy |
±0.1% FSR @ 25°C ±0.3% FSR @ -10 and 60°C |
Load Resistor | Less than 250 ohms |
• Serial Communication | |
Interface | RS-485-2w: Data+, Data-, GND |
Serial Line Protection | 15 KV ESD for all signals |
• Serial Communication Parameters | |
Parity | None |
Data Bits | 8 |
Stop Bits | 1 |
Flow Control | None |
Baudrate | 1200 to 115200 bps |
Protocol | Modbus/RTU |
• Power Requirements | |
Power Input | 24 VDC nominal, 12 to 48 VDC |
Power Consumption | 170 mA @ 24 VDC |
• Physical Characteristics | |
Wiring | I/O cable max. 14 AWG |
Dimensions | 115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in) |
Weight | 200 g |
• Environmental Limits | |
Operating Temperature | -10 to 60°C (14 to 140°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Altitude | Up to 2000 m and higher altitude on demand |
• Standards and Certifications | |
Safety | UL 508 |
EMI | FCC Part 15 Subpart B Class A, EN 55022 Class A |
EMS | IEC 61000-4, IEC 61000-6 |
Shock | IEC 60068-2-27 |
Freefall | IEC 60068-2-32 |
Vibration | IEC 60068-2-6 |
• MTBF (mean time between failures) | |
Time | 280,923 hrs |
Database | Telcordia (Bellcore) |
• Warranty | |
Warranty Period | 5 years |
Details | See www.moxa.com/warranty |