Features
16 digital inputs, 24 VDC, sink/source, dry contact type
| • Inputs and Outputs | |
| Digital Inputs | 16 channels |
| Isolation | 3K VDC or 2K Vrms |
| • Digital Inputs | |
| Sensor Type | Wet contact (NPN or PNP), dry contact |
| I/O Mode | DI or event counter |
| Dry Contact |
• On: short to GND • Off: open |
| Wet Contact (DI to GND) |
NPN (DI to GND): • On: 0 to 3 VDC • Off: 10 to 30 VDC PNP (DI to GND): • Off: 0 to 3 VDC • On: 10 to 30 VDC |
| Common Type | 8 points per COM |
| Counter Frequency | 5 kHz |
| Digital Filtering Time Interval | Software selectable (by 0.1 ms) |
| • Physical Characteristics | |
| Wiring | I/O cable, max. 16 AWG |
| Connector | Spring type terminal block |
| • Environmental Limits | |
| Operating Temperature | -40 to 75°C |
| • Power Requirements | |
| Power Consumption | 1.2 W @ 3.3 VDC |
| • MTBF (mean time between failure) | |
| Time | 1,132,561 hrs |
| Database | Telcordia (Bellcore) |