ioLogik E1213


banner950x320-2(5)

Features and Benefits

Active communication with patented Active OPC Server
2-port Ethernet switch for daisy-chain topologies
Easy mass deployment and configuration with ioSearch utility
Save time and wiring cost with peer-to-peer communication
User-defined Modbus/TCP addressing
Simplify I/O managment with MXIO library on either Windows or Linux platform
Supports SNMPv1/v2c
UL/cUL Class I Division 2, ATEX Zone 2 certification
Wide operating temperature: -40 to 75°C ( -40 to 167°F )

Introduction

Daisy-chained Ethernet I/O Connection

A new daisy-chained Ethernet I/O concept is now available. The ioLogik E1210 industrial Ethernet remote I/O has two embedded Ethernet switch ports that allow information to flow to another local Ethernet device or connect to the next ioLogik in the daisy-chain.

2012-05-08_112747

Applications such as factory automation, security and surveillance systems, and tunnel monitoring, can make use of daisy-chained Ethernet for building multi-drop I/O networks over standard Ethernet cables. Many industrial automation users are familiar with the multi-drop configuration typically used in fieldbus applications. The daisy-chain function on the Ethernet remote I/O ioLogik E1210 not only increases the connection between machines and panels, but also lowers the cost of buying separate Ethernet switches, and at the same time reduces labor fees and cabling by a large percentage. For example, if a production facility contains 700 stations (20 points per station), the wiring cost reduction can reach 15% of the total implementation cost.

Saving Time and Wiring Costs with Peer-to-Peer Communications

In remote automation applications, the control room and sensors are often far removed, making wiring over long distances a constant challenge. With peer-to-peer networking, users may now map a pair of ioLogik E1200 series modules so that input values will be directly transferred to output channels, greatly simplifying the wiring process and reducing wiring costs.

2012-05-08_112803

User-definable Modbus/TCP Addressing for Painless Upgrading of Existing Systems

For Modbus devices that are controlled and detected by fixed addresses, users need to spend a vast amount of time researching and verifying the configurations. Users need to locate each device’s networking details like I/O channels, or vendor-defined addresses to enable the initial or start address of a SCADA system or PLC. The ioLogik E1200, with user-definable Modbus/TCP addressing, offers greater flexibility, and setup is easy. Instead of worrying about individual devices, users simply configure the function and address map to fit their needs.

2012-05-08_112816
d1
d2
E1210
Inputs and Outputs
Digital Inputs 8 channels
Digital Outputs 4 channels
Digital Input/Output (configurable by jumper) 4 channels
Isolation 3K VDC or 2K Vrms
Digital Input
Sensor Type NPN, PNP, and dry contact
I/O Mode DI or event counter
Dry Contact • Logic 0: short to GND
• Logic 1: open
Wet Contact • Logic 0: 0 to 3 VDC
• Logic 1: 10 to 30 VDC (DI COM to DI)
Common Type 12 points per COM
Counter/Frequency 250 Hz, power off storage
Digital Output
I/O Mode DO or Pulse Output
I/O Type Source
Current 500 mA per channel
Voltage 15 to 30 VDC (12 or 9 VDC configurable by jumper on the 4 DO channels)
Pulse Wave Width/Frequency 1 ms/500 Hz
Over-Voltage Protection 41 VDC
Over-Current Limit 1.5 A per channel @ 25°C
Over-Temperature Shutdown 175°C (typical), 150°C (min.)
Output Current Rating 0.5 A per channel
Power Requirements
Power Input 24 VDC nominal, 12 to 36 VDC
Power Consumption 130 mA typical @ 24 VDC
LAN
Ethernet 2 x 10/100 Mbps switch ports, RJ45
Protection 1.5 kV magnetic isolation
Protocols Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP
Power Requirements
Power Input 24 VDC nominal, 12 to 36 VDC
Physical Characteristics
Wiring I/O cable max. 14 AWG
Dimensions 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
Weight Under 200 g
Mounting DIN rail or wall
Environmental Limits
Operating Temperature Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Altitude Up to 2000 m
Note Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Standards and Certifications
Safety UL 508
EMI EN 55022; EN 61000-3-2; EN 61000-3-3;
FCC Part 15, Subpart B, Class A
EMS EN 55024, EN 61000-4-2, EN 61000-4-3,
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6,
EN 61000-4-8, EN 61000-4-11
Shock IEC 60068-2-27
Freefall IEC 60068-2-32
Vibration IEC 60068-2-6
Green Product RoHS, CRoHS, WEEE
Hazardous Location UL/cUL Class I Diision 2, ATEX Zone 2
Warranty
Warranty Period 5 years (excluding ioLogik E1214)
Details See www.moxa.com/warranty
Note Because of the limited lifetime of power relays, products that use this component are covered by a 2-year warranty.