Features and Benefits
Active communication with patented Active OPC Server
2-port Ethernet switch for daisy-chain topologies
Easy mass deployment and configuration with ioSearch utility
Save time and wiring cost with peer-to-peer communication
User-defined Modbus/TCP addressing
Simplify I/O managment with MXIO library on either Windows or Linux platform
Supports SNMPv1/v2c
UL/cUL Class I Division 2, ATEX Zone 2 certification
Wide operating temperature: -40 to 75°C ( -40 to 167°F )
Introduction
Daisy-chained Ethernet I/O Connection
A new daisy-chained Ethernet I/O concept is now available. The ioLogik E1210 industrial Ethernet remote I/O has two embedded Ethernet switch ports that allow information to flow to another local Ethernet device or connect to the next ioLogik in the daisy-chain.

Applications such as factory automation, security and surveillance systems, and tunnel monitoring, can make use of daisy-chained Ethernet for building multi-drop I/O networks over standard Ethernet cables. Many industrial automation users are familiar with the multi-drop configuration typically used in fieldbus applications. The daisy-chain function on the Ethernet remote I/O ioLogik E1210 not only increases the connection between machines and panels, but also lowers the cost of buying separate Ethernet switches, and at the same time reduces labor fees and cabling by a large percentage. For example, if a production facility contains 700 stations (20 points per station), the wiring cost reduction can reach 15% of the total implementation cost.
Saving Time and Wiring Costs with Peer-to-Peer Communications
In remote automation applications, the control room and sensors are often far removed, making wiring over long distances a constant challenge. With peer-to-peer networking, users may now map a pair of ioLogik E1200 series modules so that input values will be directly transferred to output channels, greatly simplifying the wiring process and reducing wiring costs.

User-definable Modbus/TCP Addressing for Painless Upgrading of Existing Systems
For Modbus devices that are controlled and detected by fixed addresses, users need to spend a vast amount of time researching and verifying the configurations. Users need to locate each device’s networking details like I/O channels, or vendor-defined addresses to enable the initial or start address of a SCADA system or PLC. The ioLogik E1200, with user-definable Modbus/TCP addressing, offers greater flexibility, and setup is easy. Instead of worrying about individual devices, users simply configure the function and address map to fit their needs.

• Inputs and Outputs | |
Digital Inputs | 8 channels |
Digital Outputs | 4 channels |
Digital Input/Output (configurable by jumper) | 4 channels |
Isolation | 3K VDC or 2K Vrms |
• Digital Input | |
Sensor Type | NPN, PNP, and dry contact |
I/O Mode | DI or event counter |
Dry Contact | • Logic 0: short to GND • Logic 1: open |
Wet Contact | • Logic 0: 0 to 3 VDC • Logic 1: 10 to 30 VDC (DI COM to DI) |
Common Type | 12 points per COM |
Counter/Frequency | 250 Hz, power off storage |
• Digital Output | |
I/O Mode | DO or Pulse Output |
I/O Type | Source |
Current | 500 mA per channel |
Voltage | 15 to 30 VDC (12 or 9 VDC configurable by jumper on the 4 DO channels) |
Pulse Wave Width/Frequency | 1 ms/500 Hz |
Over-Voltage Protection | 41 VDC |
Over-Current Limit | 1.5 A per channel @ 25°C |
Over-Temperature Shutdown | 175°C (typical), 150°C (min.) |
Output Current Rating | 0.5 A per channel |
• Power Requirements | |
Power Input | 24 VDC nominal, 12 to 36 VDC |
Power Consumption | 130 mA typical @ 24 VDC |
• LAN | |
Ethernet | 2 x 10/100 Mbps switch ports, RJ45 |
Protection | 1.5 kV magnetic isolation |
Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP |
• Power Requirements | |
Power Input | 24 VDC nominal, 12 to 36 VDC |
• Physical Characteristics | |
Wiring | I/O cable max. 14 AWG |
Dimensions | 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in) |
Weight | Under 200 g |
Mounting | DIN rail or wall |
• Environmental Limits | |
Operating Temperature | Standard Models: -10 to 60°C (14 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Altitude | Up to 2000 m |
Note | Please contact Moxa if you require products guaranteed to function properly at higher altitudes. |
• Standards and Certifications | |
Safety | UL 508 |
EMI | EN 55022; EN 61000-3-2; EN 61000-3-3; FCC Part 15, Subpart B, Class A |
EMS | EN 55024, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11 |
Shock | IEC 60068-2-27 |
Freefall | IEC 60068-2-32 |
Vibration | IEC 60068-2-6 |
Green Product | RoHS, CRoHS, WEEE |
Hazardous Location | UL/cUL Class I Diision 2, ATEX Zone 2 |
• Warranty | |
Warranty Period | 5 years (excluding ioLogik E1214) |
Details | See www.moxa.com/warranty |
Note | Because of the limited lifetime of power relays, products that use this component are covered by a 2-year warranty. |