Features and Benefits
- Active communication with patented Active OPC Server
- Smart Alarm management with email, SNMP Trap, TCP, UDP
- Supports SNMPv1/v2c/v3 protocol
- Save time and wiring costs with peer-to-peer communication
- Front-end intelligent with patented Click&Go control logic, up to 24 rules
- Friendly configuration with web browser
Introduction
Moxa’s ioLogik E2200 is a new type of Ethernet micro RTU controller, which is a PC-based data acquisition and control device that uses proactive, event-based reporting to control I/O devices. Unlike traditional RTUs, which are passive and must poll for data, Moxa’s ioLogik E2200 series with Active OPC Server makes seamless connection with SCADA systems a reality. In addition, SNMP is used for communicating with an NMS (Network Management System) for IT field users. The I/O status of an Ethernet micro RTU controller can be reported and controlled automatically on-site based on user specified conditions. This report-by-exception approach, which is new to PC-based monitoring, requires far less bandwidth than traditional polling methods.
Active Alarming with Local Intelligence
The ioLogik E2200 Micro RTU supports simple and powerful Click&Go™ technology to deliver event-driven reports and allow alarm messages to be sent by email, TCP/UDP, and SMNP Trap with real-time stamps. With built-in Click&Go™ intelligence, the ioLogik E2200 micro RTU can be used for simple output control when it is triggered by input status, without the need for a PC controller. The ioLogik E2200 micro RTU reports I/O status automatically based on user-specified conditions. This report by-exception approach requires far less bandwidth than the traditional polling approach.
• LAN | |
Ethernet | 1 x 10/100 Mbps, RJ45 |
Protection | 1.5 KV magnetic isolation |
Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP, HTTP, CGI, SNTP, SMTP |
• Serial Communication | |
Interface | RS-485-2w: Data+, Data-, GND (3-contact terminal block) |
Serial Line Protection | 15 KV ESD for all signals |
• Serial Communication Parameters | |
Parity | None |
Data Bits | 8 |
Stop Bits | 1 |
Flow Control | None |
Baudrate | 1200 to 115200 bps |
Protocol | Modbus/RTU |
• Inputs and Outputs | |
Digital Inputs | 12 channels |
Digital Outputs | 8 channels |
• Digital Input | |
Sensor Type | Wet Contact (NPN), Dry Contact |
I/O Mode | DI or Event Counter |
Dry Contact |
• On: short to GND • Off: open |
Wet Contact (DI to GND) |
• On: 0 to 3 VDC • Off: 10 to 30 VDC |
Common Type | 12 points per COM |
Isolation | 3K VDC or 2K Vrms |
Counter Frequency | 900 Hz |
Digital Filtering Time Interval | Software selectable |
• Digital Output | |
Type | Sink |
I/O Mode | DO or Pulse Output |
Pulse Output Frequency | 1 kHz |
Over-voltage Protection | 45 VDC |
Over-current Protection | 2.6 A (4 channels @ 650 mA) |
Over-temperature Shutdown | 175°C (min.) |
Current Rating | 200 mA per channel |
Isolation | 3K VDC or 2K Vrms |
• Power Requirements | |
Power Input | 24 VDC nominal, 12 to 36 VDC |
Power Consumption | 203 mA @ 24 VDC |
• Physical Characteristics | |
Wiring | I/O cable max. 14 AWG |
Dimensions | 115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in) |
Weight | under 250 g |
Mounting | DIN-rail or wall |
• Environmental Limits | |
Operating Temperature | -10 to 60°C (14 to 140°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Altitude | Up to 2000 m and higher altitude on demand |
• Standards and Certifications | |
Safety | UL 508 |
EMI |
EN 61000-3-2; EN 61000-3-3; EN 61000-6-4; FCC Part 15, Subpart B, Class A |
EMS |
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11, EN 61000-6-2 |
Shock | IEC 60068-2-27 |
Freefall | IEC 60068-2-32 |
Vibration | IEC 60068-2-6 |
Green Product | RoHS, CRoHS, WEEE |
• MTBF (mean time between failure) | |
Time | 213,673 hrs |
Database | Telcordia (Bellcore) |
• Warranty | |
Warranty Period | 5 years |
Details | See www.moxa.com/warranty |